CELLGUARD™ Wired Legacy
CELLGUARD™ Wired Legacy
The CELLGUARD™ Wired Battery Monitoring System (BMS) delivers economical, yet highly accurate and reliable remote health analysis of stationary batteries in applications with high electromagnetic noise.
Utility personnel are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted uptime when it matters the most.
The CELLGUARD™ Wired Battery Monitoring System ideal for all mission-critical DC power plants including UPS, data center, rail / subway, airport, telco, utility power generation, utility substation, and manufacturing, as well as fire and safety systems.
BATTERY SENSORS
One battery sensor module per battery is capable of monitoring internal resistance, voltage, and temperature, delivering a comprehensive battery state of health analysis.
CONTROL MODULE
The control module records critical performance elements including alarms and discharge events. Alarm parameters and thresholds are managed through the control module which also delivers real-time system data through the web-based CELLTRAQ™ Battery Asset Management Software.
The Control Module can communicate via RS485, Ethernet, MODBUS/RTU, MODBUS/TCP, and SNMP protocols. Data derived from the BMS is easily integrated into most third-party systems.
STRING SENSOR & CURRENT TRANSDUCER
One string sensor module per string, in conjunction with a string current transducer provides monitoring of the string voltage, current, and ambient temperature.
Users can remotely access battery performance data and configure measurement parameters and thresholds via the CELLTRAQ™ Battery Asset Management Software.
BATTERY STRING STATE-OF-HEALTH
Get real-time access to critical battery and string performance and resistance data including threshold warnings and alarms.
CONSOLIDATED DATA
Multi-string and multi-site management is made intuitive and easy with centralized access to the battery performance data of an entire network.
PERFORMANCE REPORTING
Analyze and configure reporting data for all sites and strings with user-customized reports that can be exported as PDFs or spreadsheets for simplified compliance reporting.
ONCE THE PRODUCT SHIPS, WE'RE JUST GETTING STARTED
The Franklin Electric Grid Solution Technical and Field Support Teams are here to assist with training, installation, and support. Our Field team will come to your site for training or installation supervision and our Support Center staff is available to assist with troubleshooting, warranty processing, and software installation support.
System Components
1. Control Module
2. Battery Sensor Module
3. String Sensor Module
4. Current Transducer
6. CELLTRAQ Data Management Software
Specifications
Environmental Measurements
- Operating temperature: -10°C to 50°C
- Humidity: 5% to 95%
Monitoring Capability
- Maximum batteries on a single String: 180
- Control module string maximum: 6
- Control module battery maximum: 360
Specifications
- Battery types: 1.2V, 2V, 6V, 12V (capacity less than 3000AH)
- Insulation: 2000 VAC
- Weight (Coordinator): 0.3 Kg
- Weight (Battery Sensor): 75 g
- Weight (String Sensor): 80 g
Controller Module Communication Interfaces
- Serial Comm. Port: RS485 Modbus/RTU
- RJ45 Ethernet Comm. Port: SNMP, Modbus/TCP
- RJ22 Module Comm. Port: COM1-COM3 UART
Power Requirements
- Base coordinator unit: 14-36 VDC 40W, external power supplies available
- Battery sensor: < 13mA (1.2V, 2V) or 7mA (6V, 12V) from battery
- String sensor: 10.8 to 13.8VDC, 2W, power from control module
Approvals & Certifications
- EMC Certification: CISPR 11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11
- Compliance: CE & FCC
Reliability
- Auto reboot trigger: Build-in WDT
- MTBF: 100,000 hours
Measurement & Accuracy
Component | Range | Accuracy |
String Voltage | 20 to 800V | +/- 0.5% |
Battery voltage | 1.2V, 2V, 6V, 12V | +/- 0.1% |
Battery resistance | 50 to 65535uΏ | +/- 2%, 1uΏ |
Battery temperature | -5°C to 99.9°C | +/- 1°C |
String current | 0 to 1000A | +/- 2% |
Ambient temperature | -5°C to 99.9°C | +/- 1°C |
STRING SENSOR KIT
Model | Description |
---|---|
CGTC3-600-WD | CELLGUARD™ wired battery monitoring string sensor module with ambient temperature sensor, 1000A maximum, includes current transducer |
Included in the Kit
- Temperature/Current (TC) Module
- Current Transducer
- Interconnect Return Cable, 8 meter, with RJ22 plugs
- Spare RJ22 plugs (qty 18)
- Interconnect Cable, 30 cm, with RJ22 plugs
- Current Transducer Cable with Temperature Sensor
BATTERY INTERCONNECT CABLES
Model | Description |
---|---|
CGS3-70CBL-WD | CELLGUARD™ wired battery interconnect cable, 70 cm, with RJ22 plugs |
CGS3-800CBL-WD | CELLGUARD™ wired battery interconnect cable, 8 m, with RJ22 plugs |
CGS3-RJ22-WD | CELLGUARD™ spare RJ22 plugs (qty 100) |
CGS3-100CBL-WD | CELLGUARD™ wired battery interconnect cable, 100 cm, with RJ22 plugs |
CGS3-30CBL-WD | CELLGUARD™ wired battery interconnect cable, 30 cm, with RJ22 plugs |
BATTERY TABS (8 Packs)
8 packs of battery tabs are included with CELLGUARD™ Wired Battery Monitoring systems at no cost, however, quantities must be specified upon ordering.
Model | Description |
---|---|
429-0000015 | CELLGUARD™ wired battery tab, 8 mm, U-type (qty 8) |
429-0000017 | CELLGUARD™ wired battery tab, 8 mm, Ring (qty 8) |
429-0000016 | CELLGUARD™ wired battery tab, 6.5 mm, Ring (qty 8) |
429-0000018 | CELLGUARD™ wired battery tab, 10 mm, U-type (qty 8) Model |
Featured Downloads
Brochures
Title | Type | Size | |
---|---|---|---|
FEGRID-0002 CELLGUARD Wired Battery Monitoring Brochure.pdf | 4.43 MB | ||
FEGRID-0001 CELLGUARD Wired BMS Datasheet.pdf | 2.72 MB | ||
FEGRID-0014 Battery Monitoring Solutions Brochure.pdf | 9.16 MB | ||
FEGRID-0017 FE Grid Academy Certified Installer Training Brochure.pdf | 13.13 MB |
Manuals
Title | Type | Size | |
---|---|---|---|
167-000800 Cellguard Wired Battery Monitoring System Install Guide.pdf | 8.1 MB | ||