CELLGUARD™ Wired

CELLGUARD™ Wired

The CELLGUARD™ wired Battery Monitoring System (BMS) delivers economical, yet highly accurate and reliable remote health analysis of stationary batteries in applications with high electromagnetic noise. Battery operators are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted power when it matters the most.

ENSURE UPTIME WITH 24/7 MONITORING

Utility personnel are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted uptime when it matters the most.

KEY ADVANTAGES

Wired-Icon-Battery-Health.psd

STATE OF HEALTH

The BMS helps analyze data trends related to battery state of health, simplifying the detection of potential issues for operators to optimize battery usage.

LTC Icon Regulate.psd

INTERNAL RESISTANCE TESTING AND PERFORMANCE TRENDING

The BMS tests a given battery’s internal resistance at a pre-determined interval. The results are then collected and presented as a trend providing the user with genuine DC power plant performance insight.

DTM - Icon - Power Factor.psd

DISCHARGE EVENTS

Battery discharge events are recorded automatically (including battery voltage, string voltage, discharge current and discharge capacity).

Wired-Icon-Parameter.psd

PARAMETER AND ALARM THRESHOLDS

The user can set / modify many measurement parameters and thresholds either locally or remotely. The system invokes a permission hierarchy to manage administrative access.

CELLGUARD Wired - Install - Wide.psd
SOLID HARDWARE

The CELLGUARD™ Wired Battery Monitoring System ideal for all mission-critical DC power plants including UPS, data center, rail / subway, airport, telco, utility power generation, utility substation, and manufacturing, as well as fire and safety systems.

Wired - Hardware - Sensors.psd

BATTERY SENSORS

One battery sensor per battery is capable of monitoring internal resistance, voltage, and temperature, delivering a comprehensive battery state of health analysis.

UNITE-Wired-Hardware.psd

BASE COORDINATOR UNIT

The base coordinator unit (BCU) records critical performance elements including alarms and discharge events. Alarm parameters and thresholds are managed through the BCU which also delivers real-time system data through the web-based UNITE™ Battery Asset Management Software.

The BCU can communicate via RS485, Ethernet, MODBUS/RTU, MODBUS/TCP, and SNMP protocols.  Data derived from the BMS is easily integrated into most third-party systems. 

Wired - Hardware - String.psd

STRING SENSOR & CURRENT TRANSDUCER

One string sensor per string, in conjunction with a string current transducer provides monitoring of the string voltage, current, and ambient temperature.

UNITE Grid Overview Wide-Wired.psd
SOFTWARE FEATURES

 

UNITE™ allows you to seamlessly and remotely drill down through your network of battery plants, strings, and individual batteries. Gain access to valuable performance insight data, enable cost-saving condition-based maintenance planning, and simplify your compliance reporting.

UNITE Grid Battery - Report.psd

SIMPLIFY REPORTING

With a single click, a battery string report PDF can be generated to streamline reporting and compliance requirements. Reports include the latest battery data, a string overview table and graph, battery reference information, battery threshold details, and more.

UNITE Grid Battery - Map.psd

PLANT MAP VIEW

Visualize your entire plant network geographically in a single map view. Visually confirm the status of all plants and quickly key in on those that may require attention or maintenance.


UNITE Grid Battery - Battery.psd

BATTERY VIEW

Dive into the present and historical performance data of individual batteries within a string. Visualize key battery performance indicators and trending data to pinpoint batteries in need of replacement with accuracy.

UNITE Grid Battery - Discharge.psd

DISCHARGE VIEW

UNITE™ provides a graphical timeline view of every string discharge event for advanced performance analysis and NERC compliance reporting. Discharge data includes start time, end time, voltage, temperature, and current.


 

ONCE THE PRODUCT SHIPS, WE'RE JUST GETTING STARTED

 

The Franklin Electric Grid Solution Technical and Field Support Teams are here to assist with training, installation, and support. Our Field team will come to your site for training or installation supervision and our Support Center staff is available to assist with troubleshooting, warranty processing, and software installation support.

Specifications

Base Coordinator Unit (BCU)

BCU Power Requirements 14 - 36 VDC @ 40 W, external power supplies available
Battery Sensor Power Requirements < 13 mA (2 VDC) or 7 mA (4 VDC, 6 VDC, 12 VDC) from battery
String Sensor Power Requirements 10.8 - 13.8 VDC @ 2 W, power from control module
Reliability:
Auto Reboot Trigger
MTBF

Build-in WDT
100,000 hours
Approvals & Certifications:
EMC Certification
Compliance

CISPR 11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11
CE & FCC
Operating Temperature
14° to 122° F (-10° to 50° C)
Relative Humidity
5% - 95% (non condensing)
Maximum Batteries on a Single String
120
Base Coordinator Unit String Maximum
6
Base Coordinator Unit Battery Maximum
360
Battery Voltages
2 VDC, 4 VDC, 6 VDC, 12 VDC (capacity less than 3000 Ah)
Electrical Insulation
2000 VAC
Weight (Coordinator)
0.3 kg
Weight (Battery Sensor)
75 g
Weight (String Sensor)
80 g
USB B Comm Port
HTTPS
RJ45 Ethernet Comm. Port
SNMPv3, Modbus/TCP, MQTTS, HTTPS
RJ22 Module Comm. Port
3 sensor COM ports

 

 

 

 

 

 

 

Measurement & Accuracy

Component Range Accuracy
String Voltage 20 to 800 VDC +/- 0.5%
Battery Voltage 2 VDC, 4 VDC, 6 VDC, 12 VDC +/- 0.1%
Battery Internal Resistance 50 to 65535uΏ +/- 2%, 1uΏ
Battery Temperature 23° to 211.8° F (-5° to 99.9° C) +/- 1.8° F (+/- 1° C)
String Current 0 to 1000A +/- 2%
Ambient Temperature 23° to 211.8° F (-5° to 99.9° C) +/- 1.8° F (+/- 1° C)

 

 

 

 

 

 

System Components

cellguard-base-systemcomponents-01.png

1. Control Module

2. Battery Sensor Module

3. String Sensor Module

4. Current Transducer

5. UNITE™ Asset Management Database

Dimensions

cellguard-base-specs-01.png

1. Alarm indicator lights

2. Power input

3. String sensor power

4. Dry contact relays 

5. AUX inputs

6. USB-B, USB-A and Ethernet

7. Sensor Communication Ports

BATTERY SENSOR

cellguard-batterysensor-specs-01.png

Battery Sensor Components

1. Indicator light

2. Battery connection port

3. Communication ports

STRING SENSOR

cellguard-stringsensor-specs-01.png

String Sensor Components

1. Indicator light

2. Battery sensor connection port

3. Communication ports

4. Power input

Model Description
CGBC-350-HWD CELLGUARD™ Wired Base Coordinator Unit

POWER SUPPLY

Model Description
CGBC-DC-72-WD Power supply for 18-72 VDC. Includes input and output wiring.
CGBC-DC-370-WD Power Supply for 120-370 VDC. Includes input and output wiring.
CGBC-DC-1500-WD Power supply for 200-1500 VDC. Includes input and output wiring.
CGBC-AC-1224-WD Power Supply for 85-264 VAC. Includes Type – A wall outlet (NEMA1-15) for North America.

BATTERY SENSOR

Model Description
CGS3-02V-WD CELLGUARD™ wired battery monitoring battery sensor module for 2 VDC batteries
CGS3-04V-WD CELLGUARD™ wired battery monitoring battery sensor module for 4 VDC batteries
CGS3-06V-WD CELLGUARD™ wired battery monitoring battery sensor module for 6 VDC batteries
CGS3-12V-WD CELLGUARD™ wired battery monitoring battery sensor module for 12 VDC batteries.

STRING SENSOR KIT

Model Description
CGTC3-600-WD CELLGUARD™ wired battery monitoring string sensor module with ambient temperature sensor and current transducer

Included in the Kit

  • Temperature/Current (TC) Module
  • Current Transducer
  • Interconnect Return Cable, 26.2 ft (8 m), with RJ22 plugs
  • Spare RJ22 plugs (qty 18)
  • Interconnect Cable, 11.8 in (30 cm), with RJ22 plugs
  • Current Transducer Cable with Temperature Sensor

SENSOR ADDRESSING MODULE

Model Description
CGS3-AMM-WD Sensor module address modifier

BATTERY HARNESSES

Model Description
CGS3-25BH-WD CELLGUARD™ wired battery harness, 9.8 in (25 cm)
CGS3-50BH-WD CELLGUARD™ wired battery harness, 19.7 in (50 cm)
CGS3-80BH-WD CELLGUARD™ wired battery harness, 31.5 in (80 cm)

BATTERY INTERCONNECT CABLES

Model Description
CGS3-30CBL-WD 11.8 in (30 cm) interconnect cable with RJ22 plugs
CGS3-70CBL-WD 27.6 in (70 cm) interconnect cable with RJ22 plugs
CGS3-100CBL-WD 39.4 in (100 cm) interconnect cable with RJ22 plugs
CGS3-800CBL-WD 26.2 ft (8 m) interconnect cable with RJ22 plugs
CGS3-RJ22-WD CELLGUARD™ spare RJ22 plugs (qty 100)

BATTERY TABS (8 Packs)

8 packs of battery tabs are included with CELLGUARD™ Wired Battery Monitoring systems at no cost, however, quantities must be specified upon ordering.

Model Description
429-0000015 CELLGUARD™ wired battery tab, 8 mm, U-type (qty 8)
429-0000016 CELLGUARD™ wired battery tab, 6.5 mm, Ring (qty 8)
429-0000017 CELLGUARD™ wired battery tab, 8 mm, Ring (qty 8)
429-0000018 CELLGUARD™ wired battery tab, 10 mm, U-type (qty 8) Model

BATTERY TABS (50 Packs)

Model Description
CGS3-BT6-WD CELLGUARD™ wired battery tab, 6.5 mm, Ring (qty 50)
CGS3-BT8-WD CELLGUARD™ wired battery tab, 8 mm, Ring (qty 50)